Water Blocked P30 RFOU-HCF / TFOU-HCF 6/10(12) kV
Applications
-
These cables are partially water blocked, fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100˚C hydrocarbon fire.
标准
IEC 60092-354 | IEC 60092-351 |
IEC 60092-359 | IEC 60332-1 |
IEC 60331-21 | IEC 60332-3-22 |
IEC 60754-1,2 | IEC 61034-1,2 |
NEK 606:2004 | VG 95218 part 29 |
Construction
-
l Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
l Conductor Screen: Semi conducting material.
l Insulation: Halogen-free EPR. XLPE can be offered as an option.
l Insulation Screen: Semi conducting material and tinned copper wire braid.
l Filler: Water blocking fillers, if required.
l Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
l Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
l Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
l Inner Sheath: Halogen free thermosetting compound, SHF2, coloured red.
l HC-fire protection: Extruded thermoplastic fire protection compound.
l Taping: Lapped glass fibre tape.l Outer Sheath 1: Flame retardant halogen-free thermoplastic compound, SHF1, coloured red.
l Outer Sheath 2: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Optional
- P31 RFOU-HCF / TFOU-HCF 8.7/15kV
- P32 RFOU-HCF / TFOU-HCF 12/20(24) kV
- P33 RFOU-HCF / TFOU-HCF 18/30(36) kV
Electrical Characteristics
-
Nominal Cross Section Area mm² 70 95 120 150 185 240 300 Nominal Conductor Diameter mm 10.3 12.2 13.8 15.1 17.0 19.6 21.9 Maximum DC Resistant@20℃ Ω/km 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607 Continuous Current Rating@45℃1 Core A 242 293 339 389 444 522 601 Continuous Current Rating@45℃3 Core A 169 205 237 272 311 365 421 Short Circuit Current 1s A 10020 13590 17170 21460 26470 34340 42930 Operating Voltage KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
Ambient Temperature Correction Factors
-
Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80 Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Mechanical and Thermal Properties
- Bending Radius : 25×OD (during installation); 12×OD (fixed installed).
- Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight
Construction No. of cores×Cross section (mm²) |
|||||
Nominal Insulation Thickness mm |
Nominal Diameter Over Bedding mm |
Nominal Diameter Over Inner Sheath mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
|
1×70 | 3.4 | 23.5 | 30 | 64.4±2 | 5481 |
1×95 | 3.4 | 25.5 | 32 | 67.3±2 | 6195 |
1×120 | 3.4 | 27.5 | 34 | 69.3±2 | 6657 |
1×150 | 3.4 | 28.5 | 35 | 70.3±2 | 7004 |
1×185 | 3.4 | 30.5 | 36.5 | 71.8±2 | 7686 |
1×240 | 3.4 | 33 | 39 | 75.2±2 | 8663 |
1×300 | 3.4 | 35 | 41.5 | 77.7±2 | 9744 |
3×50 | 3.4 | 47 | 55 | 91.4±2 | 11519 |
3×95 | 3.4 | 54 | 62.5 | 99.8±2 | 14942 |
3×150 | 3.4 | 60 | 70.5 | 108.8±2 | 18270 |